  ? phoenix contact - 12/2005 data sheet interface 100036_04_en 1 phoenix contact gmbh & co. kg ? 32823 blomberg  germany phone: +49 - 52 35 - 30 0  fax: +49 - 52 35 - 34 12 00  www.phoenixcontact.com www.phoenixcontact.com/salesnetwork quint-ps-3x400-500ac/24dc/40 description quint power devices are 60...960 w dc power supply units for universal use. this is ensured by the wide-range input, single and three-phase versions, and an international approval package. quint power stands for guaranteed supply: powerful capacitors ensure mains buffering of more than 20 ms at full load. all three-phase devices provide the full output power, even in the event of a continuous phase failure. the power boost power reserve starts loads with high inrush currents and ensures that fuses are reliably tripped. preventive function monitoring diagnoses impermissible operating states and minimizes downtimes in your system. an active transistor output and a floating relay contact are used for remote monitoring. all quint power devices are idling-proof and short- circuit proof, and are available with a regulated and adjustable output voltage of 12, 24, and 48 v dc with output currents of 2.5, 5, 10, 20, 30, and 40 a. power supply units for use in ex zone 2, uninterruptible solutions, as-i power supply units, and a quint diode complete the product range. quint power is a built-in device. installation and startup must only be carried out by qualified personnel. the relevant country- specific regulations (e.g., vde, din) must also be observed. danger the device contains dangerous live elements and high levels of stored energy. never carry out work when the power is turned on. risk of burns the housing temperature can reach high values depending on the ambient temperature and the load of the device. make sure you always use the latest documentation. it can be downloaded at www.download.phoenixcontact.com . a conversion table is available on the internet at www.download.phoenixcontact.com/general/7000_en_00.pdf . this data sheet is valid for all products listed on the following page: 3-phase primary-switched power supply unit
quint-ps-3x400-500ac/24dc/40 100036_04_en phoenix contact 2 ordering data technical data product description type order no. pcs./pkt. 3-phase primary-switched power supply unit quint-ps-3x400-500ac/24dc/40 29 38 64 6 1 input data nominal input voltage range 3 x 400...500 v ac input voltage range 320...575 v ac (for all three phases), 450...800 v dc frequency range 45...65 hz (0 hz at dc input) current consumption 2.8 a (for all three phases at 400 v ac (nominal load)), approximately 2.2 a (for all three phases at 480 v ac (nominal load)), approximately inrush current surge < 20 a (typical), inrush current limiting/ 2 t (25c): < 1 a2s mains buffering (for nominal load) > 20 ms (at 3 x 400 v ac), > 20 ms (at 3 x 480 v ac) typical switch-on time < 1 s protective circuit transient surge protection varistor input fuse external via 3 circuit breakers 6 a, 10 a or 16 a, characteristic b recommended backup fuse 3 x circuit breaker 6 a, 10 a or 16 a, characteristic b discharge current to pe < 3.5 ma connection method screw connection stripping length 8 mm output data nominal output voltage 24 v dc 1% setting range for the output voltage 22.5...28.5 v dc output current 40 a (-25...+60c) 45 a (with power boost, -25...+40c) derating above +60c: 2.5% per kelvin current limit i boost = 45 a (for short circuit), approximately system deviation < 1% (static load change 10...90%) < 2% (dynamic load change 10...90%) < 0.1% (input voltage change 10%) power dissipation maximum nominal load maximum no load 80 w 14 w efficiency > 91% for 230 v ac and nominal values rise time < 2 ms (u out (10...90%)) residual ripple/switching peaks (20 mhz) < 100 mv pp (for nominal values) parallel connection yes, to create redundant systems and increase efficiency connection method screw connection stripping length 10 mm dc ok signal output, active type of output transistor output, u out > 0.9 x u n : high signal continuous current 40 ma, maximum output voltage +24 v dc (signal) dc ok signal output, floating type of output relay contact, u out > 0.9 x u n : contact closed continuous current 1 a, maximum maximum switching voltage 30 v ac/dc, maximum
quint-ps-3x400-500ac/24dc/40 100036_04_en phoenix contact 3 general data insulation voltage input/output input/pe 4 kv ac (type test)/1.5 kv ac (routine test) 1.5 kv ac (type test)/1.5 kv ac (routine test) insulation voltage output/pe 500 v dc (type test)/500 v dc (routine test) mounting position on horizontal ns 35 din rail according to en 60715 degree of protection ip20 protection class , with pe connection mtbf > 500,000 h according to iec 61709 (sn 29500) housing version alunox (almg1), closed weight 3.500 kg dimensions (width x height x depth) 240 mm x 130 mm x 125 mm dimensions (width x height x depth) for alternative assembly 122 mm x 130 mm x 243 mm status indicators dc ok status indicator green led (u out < 0.9 x u n : led flashes) climatic data ambient temperature (operation) -25...+70c (> 60c derating) ambient temperature (storage/transport) -40...+85c maximum permissible humidity (operation) 95% (at +25c, no condensation) vibration (operation) < 15 hz, amplitude 2.5 mm according to iec 60068-2-6 15...150 hz, 2.3g, 90 minutes shock 30g in all space directions, according to iec 60068-2-27 pollution degree 2 according to en 50178 climatic class 3k3 according to en 60721 certification/standards electrical equipment of machines en 60204 (surge voltage category iii) safety transformers for switched-mode power supply units en 61558-2-17 electrical safety (of it equipment) en 60950/vde 0805 (selv) cb scheme j ul/c-ul recognized ul 60950 u industrial control equipment ul/c-ul listed ul 508 u electrical equipment for potentially explosive areas ul/c-ul recognized ul 1604, class , division 2, groups a, b, c, d shipbuilding germanischer lloyd f , abs electronic equipment for use in electrical power installations en 50178 (vde 0160) safety extra-low voltage pelv (en 60204), selv (en 60950) safe isolation din vde 0100-410 protection against electric shock din 57100-410 protection against electric shock, basic requirements for safe isolation in electrical equipment din vde 0106-101 limitation of harmonic line currents according to en 61000-3-2 device safety b (tested safety) listed
quint-ps-3x400-500ac/24dc/40 100036_04_en phoenix contact 4 structure figure 1 operating elements 1 ac input 85...264 v ac input voltage, 45...65 hz frequency 2 dc output 24 v dc output voltage (default), can be set between 22.5 and 28.5 v dc 3 dc ok output active 4 dc ok output floating 5 potentiometer (covered) 22.5...28.5 v dc 6 dc ok led 7 universal din rail adapter uta 107 block diagram figure 2 block diagram conformance with emc directive 89/336/eec and low voltage directive 73/23/eec noise immunity test according to en 61000-6-2 1 electrostatic discharge (esd) en 61000-4-2 criterion b 2 housing air discharge contact discharge level 4 15 kv 8 kv electromagnetic hf field en 61000-4-3 criterion a 3 housing frequency range field strength level 3 80...1000 mhz/1.4...2.0 ghz 10 v/m fast transients (burst) en 61000-4-4 criterion b 2 input output signal 4 kv (inst. class 4, asymmetrical: cable to ground) 2 kv (inst. class 4, symmetrical: cable to cable) 0.5 kv (level 1, asymmetrical: cable to ground) 0.5 kv (level 1, symmetrical: cable to cable) 1 kv (level 1, asymmetrical: cable to ground) surge current load (surge) en 61000-4-5 criterion b 2 input output signal 4 kv (level 4, asymmetrical) 2 kv (level 3, asymmetrical) 1 kv (level 2, asymmetrical) conducted interference en 61000-4-6 criterion a 3 input/output/signal frequency range voltage level 3, asymmetrical 0.15...80 mhz 10 v voltage dips en 61000-4-11 criterion b input mains buffering > 20 ms noise emission test according to en 61000-6-3 noise emission of housing en 55011 (en 55022) 4 class b industrial and domestic applications 1 en 61000 corresponds to iec 61000 2 criterion b: temporary adverse effects on the operating behavior, which the device corrects automatically. 3 criterion a: normal operating behavior within the specified limits. 4 en 55011 corresponds to cispr11/en 55022 corresponds to cispr22 d c dc ok 1 3 13 o u t p u t d c 2 4 v 4 0 a output dc 24v 40a d c o k dc ok a d j u s t adjust 2 2 ,5 -2 8 ,5 v 22,5-28,5v input 3 a c 400-500v input 3 ac 400-500v l1 l2 l3 qu in t p o w e r quint power 1 4 14 1 5 6 7 d c dc o k ok 13 output dc 24v 40a output dc 24v 40a 14 2 3 4 l2 pe 13 14 dc ok l1 (+) l3 (-)
quint-ps-3x400-500ac/24dc/40 100036_04_en phoenix contact 5 safety notes and warning instructions to ensure that the device can be operated safely and all functions can be used, please read these instructions carefully. installation figure 3 convection the power supply unit can be snapped onto all din rails according to en 60715 and must be mounted horizontally (connection terminal blocks facing downwards). danger the device contains dangerous live elements and high levels of stored energy. never carry out work when the power is turned on. risk of burns the housing temperature can reach high values depending on the ambient temperature and the load of the device. quint power is a built-in device. installation and startup must only be carried out by qualified personnel. the relevant country- specific regulations (e.g., vde, din) must also be observed. before startup please ensure: ? the mains has been connected correctly and protection is provided against electric shock. ? the device can be switched off outside the power supply according to en 60950 regulations (e.g., by the line protection on the primary side). ? the protective conductor is connected. ? all supply lines have sufficient fuse protection and are the correct size. ? all output cables are the correct size for the maximum device output current or have separate fuse protection. ? sufficient convection is ensured. qu in t p o w e r quint power risk of burns the housing temperature can reach high values depending on the ambient temperature and the load of the device. to ensure sufficient convection, the following minimum spacing is required between other modules: 5 cm above and below the device. no minimum spacing to other modules at the sides is required for proper operation of the device.
quint-ps-3x400-500ac/24dc/40 100036_04_en phoenix contact 6 mounting position figure 4 mounting position (dimensions in mm) flat mounting position: installation depth 125 mm (+ din rail) narrow mounting position: installation depth 243 mm (+ din rail) flat mounting position (default upon delivery) figure 5 flat mounting position assembly position the module with the din rail guideway on the top edge of the din rail and then snap it downwards. removal release the snap-on catch using a screwdriver and then detach the module from the bottom edge of the din rail. (240) (122) 115 (130) 50 230 - - quint po wer
quint-ps-3x400-500ac/24dc/40 100036_04_en phoenix contact 7 narrow mounting position figure 6 narrow mounting position a narrow mounting position can be achieved by mounting the module onto the din rail at a 90 angle. mount the din rail adapter (uta 107) as shown in figure 6. no additional assembly material is required. mounting screws: torx t10 (torque 0.8...0.9 nm). connection of various types of network: 3 x 400...500 v ac networks figure 7 illustrates the connection of various types of network. in the event of a phase failure, continuous operation is ensured with nominal power. figure 7 3 x 400...500 v ac networks + - + - + - + - l1 l2 l3 n pe l1 l2 l3 pen l1 l2 l3 n l1 l2 l3 l1 pe l2 l3 l1 l2 l3 pe l1 l2 l3 pe l1 l2 l3 pe tn-s tn-c tt it
quint-ps-3x400-500ac/24dc/40 100036_04_en phoenix contact 8 connection of the connecting cable use a screwdriver with the correct blade width for wiring. the cable cross sections listed in the table on the right can be connected. for reliable and safe-to-touch connections, strip the cable ends according to the table. input (1) the 3 x 400...500 v ac connection is made using the l1, l2, l3, and 5 screw connections. figure 8 input fuses three external thermomagnetic fuses are required to protect the device. even in the event of a phase failure, continuous operation is ensured with nominal load. recommended backup fuse 3 x circuit breaker 6 a, 10 a or 16 a, characteristic b (or equivalent). protecting the primary side the device must be installed according to the specifications of en 60950. solid stranded awg torque stripping length [mm 2 ] [nm] [mm] input 0.2...6 0.2...4 25...10 0.5...0.6 8 mm output 0.5...16 0.5...10 20...6 1.2...1.5 10 mm signal 0.5...16 0.5...10 20...6 1.2...1.5 10 mm if an external fuse is blown, this is most probably due to a device fault. in this case, the device should be checked in the factory. a suitable fuse should be provided for dc applications. it must be possible to switch off the device using a suitable disconnecting device outside the power supply. for example, primary side line protection could be used. dc ok 1 3 13 output dc 24v 40a dc ok a d ju st adjust 22,5-28,5v input 3 a c 400-500v input 3 ac 400-500v l 1 l 2 l 3 l1 l2 l3 quint power 14 1
quint-ps-3x400-500ac/24dc/40 100036_04_en phoenix contact 9 output figure 9 output connecting the output the connection is made using the "+" and "-" screw connections on the screw connection 2 . the output voltage set upon delivery is 24 v dc. the output voltage can be set on the potentiometer 5 . protecting the secondary side the device is electronically short-circuit-proof and idling- proof. in the event of an error, the output voltage is limited to a maximum of 35 v dc. signaling the two dc ok outputs are for preventive function monitoring of the power supply unit. a floating signal contact 4 and an active dc ok signal 3 are available. in addition, the dc ok led 6 can be used to evaluate the function of the power supply directly at the installation location (see "status indicator: dc ok led" on page 10). floating contact figure 10 floating contact when opened, the floating signal contact indicates that the output voltage has fallen more than 10% below the set value. signals and ohmic loads up to a maximum of 30 v and currents up to a maximum of 1 a can be switched. active signal output figure 11 active signal output the 24 v dc signal is between the "dc ok" and "-" connection terminal blocks and can be loaded with 40 ma maximum. this signal output indicates that the output voltage has fallen more than 10% below the set value when "active high" changes to "low". the dc ok signal is isolated from the power output. this ensures that a separate supply does not enter from devices connected in parallel. the 24 v dc signal can be connected directly to a logic input for evaluation. make sure that all output cables are the correct size for the maximum output current or have separate fuse protection. the cable cross sections in the secondary circuit must be large enough to keep the voltage drops on the cables as low as possible. d c dc o k ok 1 3 13 o u tp u t d c 2 4 v 4 0 a output dc 24v 40a d c o k dc ok a d ju s t adjust 2 2 , 5 - 2 8 , 5 v 22,5-28,5v input 3 a c 400-500v input 3 ac 400-500v l 1 l 2 l 3 l1 l2 l3 quint power quint power 1 4 14 5 6 d c dc o k ok 13 o utp ut d c 24v 40 a output dc 24v 40a 14 2 3 4 with heavy inductive loads, e.g., a relay, a suitable protective circuit (e.g., free-wheeling diode) is required. dc ok + + + + dc ok 13 14 - - 30 v ac/dc, 1 a, maximum dc ok 24 v dc 40 ma + + + + dc ok 13 14 - -
quint-ps-3x400-500ac/24dc/40 100036_04_en phoenix contact 10 signal loop figure 12 signal loop the two signal outputs described above can be easily combined. example: monitoring two devices use the active alarm output of device 1 and loop in the floating alarm output of device 2. in the event of an error, a group error message is output. any number of devices can be looped. this signal combination saves wiring costs and logic inputs. status indicator: dc ok led the green dc ok led enables local function evaluation in the control cabinet. function output characteristic curve figure 13 output characteristic curve at ambient operating temperatures t amb <+40 c, the device can continuously supply an i boost current at nominal voltage. in the event of heavier loads the working point demonstrates the u/i characteristic curve shown in the figure. the output current is limited to i boost . the secondary voltage is reduced until the short circuit on the secondary side is removed. the u/i characteristic curve ensures that both heavy capacitive loads and loads with dc/dc converters can be supplied by quint power in the input circuit. connected fuses are tripped. the selectivity in your system configuration is ensured at all times. ? u n = +24 v ? i n = 40 a ? i boost = 45 a ? p n = 960 w ? p boost = 1080 w dc ok + output dc ok 13 output 14 + - - ++ dc ok dc ok 13 13 14 14 ++ -- -- 12 dc ok led on flashing off active dc ok switching output u = +24 v (with reference to "-") u = 0 v (with reference to "-") u = 0 v (with reference to "-") floating dc ok output closed open open cause output voltage greater than 90% of the set voltage output voltage less than 90% of the set voltage no voltage at the output meaning output voltage and current ok quint power operating, but: ? error at the load ? current consumption greater than i boost ? output short circuit quint power not operating, because: ? no mains voltage present ? the primary side fuse has blown ? the device is faulty p boost i boost p n i n < 40 c < 60 c u [v] u out n i [a] out
quint-ps-3x400-500ac/24dc/40 100036_04_en phoenix contact 11 temperature response figure 14 temperature response at an ambient operating temperature of up to +40 c, the device continuously supplies the i boost output current. the device can supply a nominal output current of i n up to an ambient operating temperature of +60 c. the output power must be decreased by 2.5% per kelvin temperature increase for ambient operating temperatures over +60 c. at ambient operating temperatures above +70 c or in the event of a thermal overload, the device does not switch off. the output power is decreased to such an extent that device protection is provided. once the device has cooled down, the output power is increased again. parallel operation devices of the same type can be connected in parallel to increase both redundancy and power. the default setting does not have to be adjusted. if the output voltage is adjusted, an even current distribution can be ensured by precisely setting all power supply units that are operated in parallel to the same output voltage. to ensure symmetrical current distribution we recommend that all cable connections from the power supply unit to the din rail are the same length and have the same cross section. redundancy operation figure 15 redundancy operation redundant circuits are suitable for supplying systems, which place particularly high demands on operational safety. if a fault occurs in the primary circuit of the first power supply unit, the second device automatically takes over the entire power supply, without interruption, and vice versa. for this purpose, the power supply units to be connected in parallel must be large enough that the total current requirements of all loads can be fully met by one power supply unit. increasing power figure 16 increasing power the output current can be increased to n x i n where n is the number of devices connected in parallel. parallel connection for increasing power is used when extending existing systems. a parallel connection is recommended if the power supply unit does not cover the current consumption of the most powerful load. otherwise, the loads should be divided over independent individual devices. ? phoenix contact 12/2005 a maximum of five devices can be connected in parallel. depending on the system, for parallel connection of more than two power supply units a protective circuit should be installed at each individual device output (e.g., decoupling diode or dc fuse). this prevents high return currents in the event of a secondary device fault. 0 0 40 60 20 i boost i n output current [a] ambient operating temperature [ c] external decoupling diodes are required for 100% redundancy (quint-diode/40, order no. 29 38 96 3). a maximum of five devices can be connected in parallel. i n + + ++ - -- - = i n i n i n + + ++ - -- - = 2 * i n i n